PRODUCTS
Wire & Cable, Cable Accessories, Telecom Accessories, Energy Saving Lamp(CFL)...
KT1413 PH120 SR 114E Enhanced Cable
 
View Larger
KT1413 PH120 SR 114E Enhanced Cable
 
KT1413 PH120 SR 114E Enhanced Cable
APPLICATION:
These cables are used for installation in fire systems for connecting fire alarms etc. 
The cable can be installed in dry and moist areasas well for fixed open air installation. 
This cable type with electrostatic screening (St) protects the transmission circuits 
against externelectrical interferences.
Standards:
All these cables comply to: 
BS 5839-1:2002
Code of practice for fire system design, installation, commissioning and maintenance.
BS 7629-1:2008
Low emission of smoke and corrosive gases
BS EN 50200 PH120
Temperature: 830 °C Flame and shock for 120 minutes.
             
ELECTRICAL DATA (AT20OC)
Minimum  
Bend Radius
Min.
Insulation 
resistance
Max.
Working 
Temperature
Test 
voltage
(rms value)
Max. 
Operating 
voltage
8×Diameter 300 MΩ/km -40℃~+90 1000V 300/500V
             
TYPES AND MECHANICAL DATA
Types 
sqmm 
(mm2)
Conductor 
Class
Insulation Shielded Drain Wire Sheath 
Matterial
OD of 
Sheath 
(mm)
2×1.0 BC Class 1,2 Silicone Rubber PET/AL-Foil  125% TC FR-LSZH 7.00±0.20
4×1.0 BC Class 1,2 Silicone Rubber PET/AL-Foil  125% TC FR-LSZH 8.00±0.20
2×1.5 BC Class 1,2 Silicone Rubber PET/AL-Foil  125% TC FR-LSZH 7.50±0.20
4×1.5 BC Class 1,2 Silicone Rubber PET/AL-Foil  125% TC FR-LSZH 8.60±0.20
2×2.5 BC Class 1,2 Silicone Rubber PET/AL-Foil  125% TC FR-LSZH 8.50±0.20
4×2.5 BC Class 1,2 Silicone Rubber PET/AL-Foil  125% TC FR-LSZH 10.0±0.20
2×4.0 BC Class 2 Silicone Rubber PET/AL-Foil  125% TC FR-LSZH 9.80±0.20
4×4.0 BC Class 2 Silicone Rubber PET/AL-Foil  125% TC FR-LSZH 11.70±0.20
  Class 1,2          
*Notes Class Types Class1: Solid / Class 2: 7 Cores / Class 5: Flexible
  FR-LSZH: LSZH thermoplastic material Type LTS3to BS 7656-6.1
  Silicone 
Rubber:
High performance silicone rubber EI2 to BS EN 50363-1
             
TECHNICAL DATA
Types
sqmm 
(mm2)
Max.
Resistance of 
Cond.at 20
Current 
Carrying 
Capacity
(Amperes)
Nominal 
Capacitance
(pF/m)
  Class 1,2 Class 5 Clipped 
Direct
In 
Conduit
Core/
Core
Core/
Screen
1.00  18.10 Ω/km 19.50 Ω/km 19 17 100 170
1.50  12.10 Ω/km 13.30 Ω/km 24 22 110 190
2.50    7.41 Ω/km   7.98 Ω/km 33 30 130 220
4.00    4.61 Ω/km   4.95 Ω/km 45 40 160 270
             
Google Translate
Copyright © 2011 KINGTONE ELECTRONICS CO.,LTD. All rights reserved. Powered by Hi-eweb.com
Products: Coaxial cable manufacturer, Power cable manufacturer, Solar panel manufacturer, RG59 with power cable, utp cat5e