PRODUCTS
Wire & Cable, Cable Accessories, Telecom Accessories, Energy Saving Lamp(CFL)...
KT1413 PH120 SR 114E Enhanced Cable
KT1413 PH120 SR 114E Enhanced Cable
KT1413 PH120 SR 114E Enhanced Cable |
APPLICATION: |
These cables are used for installation in fire systems for connecting fire alarms etc.
The cable can be installed in dry and moist areasas well for fixed open air installation.
This cable type with electrostatic screening (St) protects the transmission circuits
against externelectrical interferences. |
Standards: |
All these cables comply to:
BS 5839-1:2002
Code of practice for fire system design, installation, commissioning and maintenance.
BS 7629-1:2008
Low emission of smoke and corrosive gases
BS EN 50200 PH120
Temperature: 830 °C Flame and shock for 120 minutes. |
|
|
|
|
|
|
|
ELECTRICAL DATA (AT20OC) |
Minimum
Bend Radius |
Min.
Insulation
resistance |
Max.
Working
Temperature |
Test
voltage
(rms value) |
Max.
Operating
voltage |
8×Diameter |
300 MΩ/km |
-40℃~+90℃ |
1000V |
300/500V |
|
|
|
|
|
|
|
TYPES AND MECHANICAL DATA |
Types
sqmm
(mm2) |
Conductor
Class |
Insulation |
Shielded |
Drain Wire |
Sheath
Matterial |
OD of
Sheath
(mm) |
2×1.0 |
BC Class 1,2 |
Silicone Rubber |
PET/AL-Foil 125% |
TC |
FR-LSZH |
7.00±0.20 |
4×1.0 |
BC Class 1,2 |
Silicone Rubber |
PET/AL-Foil 125% |
TC |
FR-LSZH |
8.00±0.20 |
2×1.5 |
BC Class 1,2 |
Silicone Rubber |
PET/AL-Foil 125% |
TC |
FR-LSZH |
7.50±0.20 |
4×1.5 |
BC Class 1,2 |
Silicone Rubber |
PET/AL-Foil 125% |
TC |
FR-LSZH |
8.60±0.20 |
2×2.5 |
BC Class 1,2 |
Silicone Rubber |
PET/AL-Foil 125% |
TC |
FR-LSZH |
8.50±0.20 |
4×2.5 |
BC Class 1,2 |
Silicone Rubber |
PET/AL-Foil 125% |
TC |
FR-LSZH |
10.0±0.20 |
2×4.0 |
BC Class 2 |
Silicone Rubber |
PET/AL-Foil 125% |
TC |
FR-LSZH |
9.80±0.20 |
4×4.0 |
BC Class 2 |
Silicone Rubber |
PET/AL-Foil 125% |
TC |
FR-LSZH |
11.70±0.20 |
|
Class 1,2 |
|
|
|
|
|
*Notes |
Class Types |
Class1: Solid / Class 2: 7 Cores / Class 5: Flexible |
|
FR-LSZH: |
LSZH thermoplastic material Type LTS3to BS 7656-6.1 |
|
Silicone
Rubber: |
High performance silicone rubber EI2 to BS EN 50363-1 |
|
|
|
|
|
|
|
TECHNICAL DATA |
Types
sqmm
(mm2) |
Max.
Resistance of
Cond.at 20℃ |
Current
Carrying
Capacity
(Amperes) |
Nominal
Capacitance
(pF/m) |
|
Class 1,2 |
Class 5 |
Clipped
Direct |
In
Conduit |
Core/
Core |
Core/
Screen |
1.00 |
18.10 Ω/km |
19.50 Ω/km |
19 |
17 |
100 |
170 |
1.50 |
12.10 Ω/km |
13.30 Ω/km |
24 |
22 |
110 |
190 |
2.50 |
7.41 Ω/km |
7.98 Ω/km |
33 |
30 |
130 |
220 |
4.00 |
4.61 Ω/km |
4.95 Ω/km |
45 |
40 |
160 |
270 |
|
|
|
|
|
|
|